Cummins Generator Cooling System
Mar 12, 2018

1. The air intake should be set on the generator side or on both sides of the generator. The area should be larger than 2.2 times the area of the tank.

2. The area of the air outlet should be 1.5 times the area of the water tank, and shutters and wind walls should be installed at the air outlet.

3. Use a flexible duct flange to connect with the tank to absorb the displacement and vibration of the unit to prevent noise transmission.

4. Hot air must be discharged to the outside of the machine room through the air duct. The cross-sectional area of the air duct should smoothly transition from small to large. If there is a bend in the air duct, a deflector must be installed to reduce the pressure loss.

5. When the ambient temperature is higher than the design temperature, consider the use of reduced power.